Model Arrester SiC Menggunakan Model Arrester ZnO IEEE WG 3.4.11

Authors

  • Herman Halomoan Sinaga Jurusan Teknik Elektro, Universitas Gajah Mada Yogyakarta
  • T. Haryono Jurusan Teknik Elektro, Universitas Lampung
  • Tumiran

:

https://doi.org/10.9744/jte.5.1.

Keywords:

Arrester Model, Arrester SiC, Transient Respons.

Abstract

Arrester model is needed to analyse the insulation coordination in power system. The model should give a suitable respon for varying transient fault. In this paper, we conduct simulation that modified from IEEE WG 3.4.11 model. The model is modified by insert a switch that voltages dependent. Arrester modeling respons then compare to the laboratory testing result, with SiC 12 kV arrester sample. Testing conduct with time front varying from 1.2 to 29.7 s with magnitude 51 kV, 52.5 kV dan 54 kV. The difference between simulation and laboratory testing was 4.332 % for sparkovervoltage and 3.259 % for residual voltage discharge current Abstract in Bahasa Indonesia : Model arrester sangat dibutuhkan untuk menganalisis koordinasi isolasi dalam suatu sistem tenaga listrik. Model arrester yang dibuat harus memberikan tanggapan yang sesuai untuk semua kondisi gangguan transient. Dalam makalah ini dihasilkan simulasi dengan menggunakan model yang dimodifikasi dari model IEEE WG 3.4.11. Model ini dimodifikasi dengan menambahkan saklar yang dipengaruhi tegangan. Hasil yang didapatkan dari pemodelan kemudian akan dibandingkan dengan pengujian di laboratorium terhadap arrester SiC 12 kV. Pengujian dilakukan dengan surja tegangan dengan waktu muka 1.2 sampai 29.7 s dan puncak tegangan diberikan sebanyak 3 tingkatan, 51 kV, 52.5 kV dan 54 kV. Perbandingan hasil pengujian dan simulasi memberikan perbedaan sebesar 4.332 % untuk tegangan potong dan 3.259 % untuk tegangan residu arus pelepasan. Kata kunci: Model Arrester, Arrester SiC, Respons Transient.

Downloads

Published

2005-04-16

Issue

Section

Articles